Efficiency against Methicillin Resistant Staphylococcus Aureus (MRSA) - Test result Korea Conformity Laboratories

Wellisair: Efficiency against Methicillin Resistant Staphylococcus Aureus (MRSA)

 

Bacteria test report (nº 027131): March 24th, 2016 Korea Conformity Laboratories (KCL).

 

Scope: measure the effectiveness of the Wellisair for the disinfection against MRSA (Methicillin Resistant Staphylococcus Aureus), bacteria contracted in hospitals through the insertion of a ventilator tube in the patient that produces a nosocomial pneumonia, a disease that can be fatal.

 

Procedure:

  • Test Method: measure the reduction rate of MRSA after injecting a constant concentration of bacteria inside a Test chamber of 8m3 for 4 hours.
  • Measurement equipment: air sampler system MAS-100NT.
  • Test Conditions: 23ºC 50,2% R.H.
 

 

 

 

 

 

Before Wellisair operating

 

 

 

 

 

After Wellisair operating

 

Results:

 

MRSA airborne concentration decay

 

Time

Before Wellisair operating

After Wellisair operating

Microbes (CFU/m3)

Microbes (CFU/m3

Reduction (%)

4h

1,0x104

<10

99,9%

 

Conclusions: Wellisair air disinfection was able to reduce 99,9% of the initial surface concentration of MRSA microbes after 4 hours of treatment.